Type | High Voltage, Outdoor |
Rated Voltage | 40.5kV |
Rated Cuttent | 1250A |
Certificated: | GB11022/GB1984/GB311.1-6 |
Mechanical Life | 10000 |
Rated frequency | 50/60Hz |
Application | Electrical Power Distribution |
OEM | logo/package |
Item | Units | parameters |
Rated voltage | KV | 40.5 |
Rated Frequency | HZ | 50 |
Rated Current | A | 1250/1600/2500 |
Rated short-circuit breaking current | KA | 20/25/31.5 |
Rated short-circuit duration | S | 4 |
Rated short-circuit breaking current breaking number | nos | 12 |
Rated operating sequence | 0-0.3s-CO-180s-CO | |
Closing time | ms | ≤ 150 |
opening time | ms | ≤ 60 |
Mechanical life | Times | 10000 |
Rated Storage and operation voltage | V | AC DC 220/110 |
Closing speed | m/s | 0.7±0.2 |
Opening speed | m/s | 1.5±0.2 |
Contact closing spring time | ms | ≤5 |
Three phase closing opening asynchrony | ms | ≤2 |